Rack Planner
List the equipment; get U used, the right rack size (wall or floor), depth, power, heat in BTU/h and patch-cord count, with a simple rack drawing.
Equipment in the rack
Watts are typical values; edit them from the datasheet. For a UPS enter only its own losses, so the load it feeds is not counted twice.
25% is typical. Spare space also helps air flow and cooling.
Patch cords
Results
Recommended rack size
15U
Wall-mount cabinet
U used
12U
U with headroom
15U
Total power
300W
Heat output
1,024BTU/h
Patch cords
Cords
24
Suggested length
0.5m
Rack drawing (top to bottom) · 15U
Devices fill from the top in list order. UPS units go at the bottom because they are the heaviest.
How we calculate
1. U used = Σ (height in U × qty). Vertical 0U PDUs are not counted. 1U = 44.45 mm.
2. U with headroom = U used × (1 + headroom), rounded up. Then the next standard rack size: 6, 9, 12, 15, 18, 22, 27, 32 or 42U.
3. Wall-mount up to 15U when there are no servers. With servers → floor-standing, ≥ 800 mm deep; without → 450–600 mm.
4. Heat in BTU/h = total watts × 3.412. Almost every watt the equipment draws ends up as heat in the rack.
5. Patch cords = one per switch port in use: 0.5 m when the switch sits next to its patch panel, 1 m when they are grouped apart.
These results are estimates to help with planning and budgeting. Our engineers will verify everything on site before final design and equipment proposal.
The same rules of thumb our engineers use for a first design. Good enough for budgeting; the final numbers come from a site survey.
How to use it and read the result
What to enter and where to find each number
Each row is one type of equipment: what it is, its height in rack units (U), the watts of one unit and how many you have.
- Height. Printed on the datasheet as 1U, 2U and so on. One U is 44.45 mm, so you can also measure the front panel. Choose "Other" to set any height yourself. A vertical PDU mounts on the side and counts as 0U.
- Watts each. The presets are typical values (switch 40 W, firewall 40 W, 1U server 300 W, 2U server 450 W, NAS 120 W, NVR 60 W). Replace them with the maximum from the datasheet or the nameplate on the back of the unit. For a server, the iDRAC, iLO or similar management page shows real consumption.
- UPS. Enter only the UPS's own losses (the presets are 60 W for 2U and 100 W for 3U). The equipment it feeds is already in the other rows, so its load must not be counted twice.
- Free space for the future. 25% by default. Empty U also lets air move between hot devices.
- Switch ports in use and layout. Count the patched ports. "Interleaved" means each switch sits directly above or below its patch panel; "grouped" means all panels together and all switches together.
How the planner works out the results
| Result | How it is worked out | What it means on site |
|---|---|---|
| U used | Σ (height × qty), 0U PDUs not counted | Space the equipment takes today |
| U with headroom | U used × (1 + headroom), rounded up | Space to buy for |
| Recommended rack | Next size up: 6, 9, 12, 15, 18, 22, 27, 32 or 42U | Above 42U the tool tells you to split into several racks |
| Cabinet type | Wall-mount up to 15U if there are no servers, otherwise floor-standing | Servers always mean floor-standing |
| Depth | 450–600 mm without servers, at least 800 mm with them (1,000 mm for long servers or sliding rails) | Check NAS, UPS and server length on the datasheet |
| Total power and heat | Σ (watts × qty); heat = W × 3.412 BTU/h | Above 1,500 W the tool warns: fans plus an air-conditioned room |
| Patch cords | One per switch port in use: 0.5 m interleaved, 1 m grouped | Order about 10% spare |
The drawing fills from the top in list order and puts UPS units at the bottom, because batteries are the heaviest thing in the rack. The 25% is the only margin. Watts are not derated, and the heat figure assumes every watt ends up as heat, which is close to true for IT equipment.
Worked example: a small office with one server
A trading office in Vientiane: 2 patch panels, 2 switches at 40 W, 2 cable managers, 1 firewall at 40 W, one 2U server at 450 W, one 2U NVR at 60 W, a 3U UPS (100 W of losses) and a horizontal PDU. 40 ports in use, panels and switches grouped.
- U used: 2 + 2 + 2 + 1 + 2 + 2 + 3 + 1 = 15U.
- With headroom: 15 × 1.25 = 18.75, rounded up to 19U, so the next size is a 22U rack.
- Type: the server makes it floor-standing, at least 800 mm deep. Without headroom 15U would fit a wall-mount size, but the server still rules it out.
- Power: 2 × 40 + 40 + 450 + 60 + 100 = 730 W. Second check: 80 + 40 = 120; 120 + 450 = 570; 570 + 60 = 630; 630 + 100 = 730.
- Heat: 730 × 3.412 = 2,490.76, shown as 2,491 BTU/h. That is under 1,500 W, so no fan warning, but a closed rack in a store room will still cook.
- Cords: 40 at 1 m. Interleave the panels and switches and they become 40 at 0.5 m. Order about 44.
For the UPS, the load is 730 − 100 = 630 W, because the 100 W is the UPS itself. Enter 630 W in the UPS runtime calculator.
The default rows on the page give a simpler case: 12U used, × 1.25 = 15U, a 15U wall-mount cabinet, 300 W and 1,024 BTU/h (300 × 3.412 = 1,023.6).
Heat, power and placement in Lao conditions
- One ton of air-conditioning removes 12,000 BTU/h. The rack in the example adds about 0.2 ton (2,491 ÷ 12,000), but the room also gains heat from lights, people and a west wall in the afternoon sun. Size the air-conditioner for the room, not only the rack.
- Hot, humid rooms shorten battery life. A UPS battery kept in a room without air-conditioning ages much faster than its rated life.
- Brownouts between 17:00 and 19:00 hit just when the air-conditioner and lights also start. Put the air-conditioner on its own circuit, not on the UPS.
- A wall-mount cabinet carrying a UPS needs a solid wall and proper anchors. Check the weight with batteries before you drill into a gypsum board partition.
- At mine sites and warehouses, dust blocks fans and filters. Plan a cleaning schedule, not just a bigger rack.
Common mistakes we see on Lao sites
- Buying the rack after the equipment, then finding the server is longer than a 600 mm cabinet.
- No free U left, so the next switch sits on top of the rack.
- Every patch cord 2–3 m long, coiled in front of the switches and blocking the air.
- The UPS mounted at the top of a wall cabinet, which makes it top-heavy and hard to service.
- No labels on ports, cords or panels. See network rack and labeling.
When the planner is not enough
The tool sizes one rack from a list. A server room with several racks, a new building, or a site where the rack has to share a room with a generator transfer switch or electrical panels needs a survey: floor loading, cooling, earthing, cable routes and access. Our server room checklist lists what we look at, and the build itself is part of our server room buildout and structured cabling work.
Next step
Send us on WhatsApp a screenshot of your planner result, a photo of the room where the rack will go, and photos of the model labels on the server and UPS. We will confirm the rack size and depth and tell you whether the room needs extra cooling.
FAQ
What size rack do I need for my network?
Add up the U of every device (1U = 44.45 mm), add about 25% free space and round up to the next standard size: 6, 9, 12, 15, 18, 22, 27, 32 or 42U. Example: 12U of equipment × 1.25 = 15U, so a 15U rack. If there is a server, use a floor-standing cabinet even when few U are used. Enter your real list in the planner to see the drawing.
Do I need a 600 mm or 800 mm deep rack?
For switches, patch panels and a firewall, 450–600 mm is enough. With a server, use at least 800 mm, and 1,000 mm for long servers or sliding rails. Check the length of the server, NAS and UPS on the datasheet before you order the cabinet, and leave room behind them for plugs and power cords.
How do I convert rack watts to BTU for air-conditioning?
Multiply the total watts by 3.412 to get BTU/h, because almost every watt IT equipment draws becomes heat. Example: 730 W × 3.412 = 2,491 BTU/h, about 0.2 ton of cooling (1 ton = 12,000 BTU/h). Add the heat from people, lights and sun on the walls. Above 1,500 W a closed cabinet needs fans and the room needs air-conditioning.
Wall-mount or floor-standing rack: which should I choose?
A wall-mount cabinet suits up to 15U including headroom when there are no servers: switches, patch panels, a firewall and a small UPS. Above that, or with any server, use floor-standing. Before hanging a wall cabinet with a UPS, check the total weight with batteries and fix it only to a solid wall, not a gypsum partition.
Related solutions
Related guides
Network Rack Layout and Labeling: So the Next Technician Finds the Cable in Five Minutes
Sizing the rack, laying out equipment, managing cables and a TIA-606 style labeling scheme, plus a maintenance schedule and advice for dusty, hot sites.
Server Room Checklist for a Hot, Humid Climate: Power, Cooling, Security and Cabling
The checklist we actually use when building or fixing server rooms in Laos: brownouts, failed AC, flooding, dust, and the documentation nobody writes.
Sizing a UPS Properly: VA, Watts, Power Factor and Real Battery Runtime
Why some 3 kVA UPS units only deliver 1,800 W, how to choose between offline, line-interactive and online, how to estimate runtime realistically, and how to pair a UPS…
Tools
Solar System Sizing Calculator
Enter kWh from your bill or a device list; get panel size (kWp), inverter, LiFePO4 battery and roof area for on-grid, hybrid and off-grid systems.
Open calculatorCCTV Storage Calculator
Enter cameras, resolution, codec and retention days; get total TB, per-camera bitrate and a drive/RAID layout for the NVR.
Open calculatorUPS Sizing & Runtime Calculator
Add up servers, switches and NAS to get a UPS rating (VA/W) with 25% headroom and the battery energy to ride through an outage.
Open calculatorInternet Bandwidth Calculator
Before you renew with your ISP: size download and upload from users, cloud apps, video calls and remote CCTV viewing.
Open calculatorWi-Fi Access Point Estimator
Counts access points two ways, by floor area and by people online at once, for Wi-Fi 6, 6E and 7. The higher number wins.
Open calculatorPoE Budget Calculator
Add up the PoE draw of cameras, APs and IP phones to get a switch budget with 20% headroom. PTZs that need 802.3bt get flagged.
Open calculatorGenerator & ATS Sizing Calculator
List what must run in an outage; get a generator size (kVA) that copes with motor starts and UPS loads, plus ATS rating and fuel per hour.
Open calculatorSubnet & VLAN Planner
Enter a base network and devices per VLAN; get non-overlapping subnets with gateway, usable range, broadcast and growth headroom, copyable as a table.
Open calculatorCCTV DORI Distance Calculator
Pick resolution, lens and sensor; get the field of view and the distances to detect, observe, recognise and identify (px/m per IEC 62676-4).
Open calculatorSend us a floor plan or a few photos of the site
We’ll come back with a few questions, then a first design. The first consultation is free, in Lao, Thai or English, on WhatsApp or our Facebook page.